Ver.2
25
(iv) List of registers
Register
No.
Function name
Function code
R/W
Monitoring and setting items
Data resolution
1103h
Acceleration time (1)
F002 (high)
R/W 1 to 360000
0.01 [s]
1104h
F002 (low)
1105h
Deceleration time (1)
F003 (high)
R/W 1 to 360000
0.01 [s]
1106h
F003 (low)
1107h
Keypad Run key routing
F004
R/W 0 (forward rotation), 1 (reverse rotation)
-
1108h to
1200h
Unused
-
-
Inaccessible
-
(v) List of registers (function modes)
Parameter group A
Register
No.
Function name
Function code
R/W
Monitoring and setting items
Data resolution
1201h
Frequency source
A001
R/W
0 (keypad potentiometer), 1 (control circuit terminal
block), 2 (digital operator), 3 (Modbus), 4 (option ), 6
(pulse train input), 7 (easy sequence), 10 (operation
function result)
-
1202h
Run command source (*)
A002
R/W
1 (control circuit terminal block), 2 (digital operator),
3 (Modbus), 4 (option)
-
1203h
Base frequency
A003
R/W 300 to "maximum frequency"
0.1 [Hz]
1204h
Maximum frequency
A004
R/W 300 to 4000(10000)
0.1 [Hz]
1205h
[AT] selection
A005
R/W
0 (switching between O and OI terminals),
2 (switching between O terminal and keypad
potentiometer),
3 (switching between OI terminal and keypad
potentiometer)
-
1206h to
120Ah
(Reserved)
-
-
-
-
120Bh
[O] input active range start
frequency
A011 (high)
R/W 0 to 40000(100000)
0.01 [Hz]
120Ch
A011 (low)
120Dh
[O] input active range end
frequency
A012 (high)
R/W 0 to 40000(100000)
0.01 [Hz]
120Eh
A012 (low)
120Fh
[O] input active range start
voltage
A013
R/W 0 to "[O]-[L] input active range end voltage"
1 [%]
1210h
[O] input active range end
voltage
A014
R/W "[O]-[L] input active range start voltage" to 100
1 [%]
1211h
[O] input start frequency
select
A015
R/W 0 (external start frequency), 1 (0 Hz)
-
1212h
Analog input filter.
A016
R/W 1 to 30 or 31 (500 ms filter ±0.1 Hz with hysteresis)
1
1213h
EzSQ selection
A017
R/W 0 (disabling), 1 (PRG terminal) , 2 (Always)
-
1214h
(Reserved)
-
-
-
-
1215h
Multi speed operation
selection
A019
R/W 0 (binary), 1 (bit)
-
1216h
Multi-speed freq. 0
A020 (high)
R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
1217h
A020 (low)
R/W
1218h
Multi-speed freq. 1
A021 (high)
R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
1219h
A021 (low)
R/W
121Ah
Multi-speed freq. 2
A022 (high)
R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
121Bh
A022 (low)
R/W
121Ch
Multi-speed freq. 3
A023 (high)
R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
121Dh
A023 (low)
R/W
121Eh
Multi-speed freq. 4
A024 (high)
R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
121Fh
A024 (low)
R/W
1220h
Multi-speed freq. 5
A025 (high)
R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
1221h
A025 (low)
R/W
1222h
Multi-speed freq. 6
A026 (high)
R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
1223h
A026 (low)
R/W
1224h
Multi-speed freq. 7
A027 (high)
R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
1225h
A027 (low)
R/W
After changing the setting, keep the time 40ms or longer before actually give run command
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......