B
42
Register
No.
Function name
Function code R/W
Monitoring and setting items
Data
resolution
142Ah
Frequency arrival setting for accel.
C042 (high)
R/W
0 to 40000
0.01 [Hz]
142Bh
C042 (low)
R/W
142Ch
Frequency arrival setting for decel.
C043 (high)
R/W
0 to 40000
0.01 [Hz]
142Dh
C043 (low)
R/W
142Eh PID deviation level
C044
R/W 0 to 1000
0.1 [%]
142Fh Frequency arrival setting 2 for
accel.
C045 (high)
R/W
0 to 40000
0.01 [Hz]
1430h
C045 (low)
R/W
1431h Frequency arrival setting 2 for
decel.
C046 (high)
R/W
0 to 40000
0.01 [Hz]
1432h
C046 (low)
R/W
1433h
Pulse train input scale conversion
for EO output
C047
R/W
0.01
– 99.99
-
1434h to
1437h
(Reserved)
-
-
-
-
1438h Maximum PID feedback data
C052
R/W 0 to 1000
0.1 [%]
1439h Minimum PID feedback data
C053
R/W 0 to 1000
0.1 [%]
143Ah Over-torque/under-torqueselection
C054
R/W
0(Over torque)/1(under torque)
-
143Bh
Over-torque (forward-driving) level
setting
C055
R/W 0 to 200
1 [%]
143Ch
Over-torque (reverse
regenerating) level setting
C056
R/W 0 to 200
1 [%]
143Dh
Over-torque (reverse driving) level
setting
C057
R/W 0 to 200
1 [%]
143Eh
Over-torque (forward
regenerating) level setting
C058
R/W 0 to 200
1 [%]
143Fh
Signal output mode of Over/under
torque
C059
R/W
00 (output during
acceleration/deceleration and
constant-speed operation), 01 (output
only during constant-speed operation)
-
1440h (Reserved)
-
-
-
-
1441h Electronic thermal warning level
C061
R/W 0 to 100
1 [%]
1442h (Reserved)
-
-
-
1443h Zero speed detection level
C063
R/W 0 to 10000
0.01 [Hz]
1444h Heat sink overheat warning level
C064
R/W 0 to 110
1 [
℃
]
1445h to
144Ah
(Reserved)
-
-
-
-
144Bh Communication speed
C071
R/W
03(2400bps), 04(4800bps),
05(9600bps) 06(19.2kbps),
07(38.4kbps),,08(57.6kbps),
09(76.8kbps), 10(115.2kbps)
-
144Ch Modbus address
C072
R/W 1. to 247.
-
144Dh (Reserved)
-
-
-
-
144Eh Communication parity
C074
R/W
00 (no parity), 01 (even parity), 02 (odd
parity)
-
144Fh Communication stop bit
C075
R/W 1 (1 bit), 2 (2 bits)
-
1450h
Selection of the operation after
communication error
C076
R/W
0 (tripping), 1 (tripping after decelerating
and stopping the motor), 2 (ignoring
errors), 3 (stopping the motor after
free-running), 4 (decelerating and
stopping the motor)
-
1451h Communication timeout limit
C077
R/W 0 to 9999
0.01 [sec.]
1452h Communication wait time
C078
R/W 0 to 1000
1 [msec.]
1453h to
1454h
(Reserved)
-
-
-
-
1455h [O] input span calibration
C081
R/W 0 to 2000
0.1
1456h [OI] input span calibration
C082
R/W 0 to 2000
0.1
1457h to
1458h
(Reserved)
-
-
-
-
1459h Thermistor input tuning
C085
R/W 0 to 2000
0.1
145Ah to
145Eh
(Reserved)
-
-
-
-
145Fh Debug mode enable
C091
R
0/1
-
1460h to
1463h
(Reserved)
-
-
-
-
1464h Communication selection
C096
R/W 0(Modbus-RTU) 1(EzCOM)
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......