4
81
Forward Rotation, Reverse Rotation Signals
Forward Rotation signal-
The inverter continues to output the forward rotation signal
(FWR) while it is driving the motor for forward operation. The FWR signal is turned off
while the inverter is driving the motor for reverse operation or stopping the motor.
Reverse Rotation signal -
The inverter continues to output the forward rotation signal
(RVR) while it is driving the motor for reverse operation. The RVR signal is turned off
while the inverter is driving the motor for forward operation or stopping the motor.
Option
Code
Terminal
Symbol
Function Name
State
Description
FWR
Forward rotation
ON
Inverter is driving the motor for forward operation
OFF
Inverter is driving the motor for reverse operation, or
the motor is stopped
RVR
Reverse rotation
ON
Inverter is driving the motor for reverse operation
OFF
Inverter is driving the motor for forward operation, or
the motor is stopped
Valid for inputs:
11, 12, AL0
– AL2
Example for terminal [11] (default output
configuration shown
– see
page 3-89
):
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration
– see
page 4-51 and 3-91
):
See I/O specs on
page 4-6
Required settings
Notes:
Output freq.
Forward rotation signal (FWR)
Reverse rotation signal (RVR)
RY
Inverter output
terminal circuit
CM2
11
FWR
AL1
Power
supply
Load
AL0
AL2
Inverter logic
circuit board
FWR
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......