Jogging Command
The Jog input [JG] is used to command
the motor to rotate slowly in small
increments for manual operation. The
speed is limited to 9.99 Hz. The
frequency for the jogging operation is
set by parameter
. Jogging does
not use an acceleration ramp, so we
recommend
setting
the
jogging
frequency
to 5 Hz or less to
prevent tripping.
When the terminal [JG] is turned ON
and the Run command is issued, the
inverter outputs the programmed jog
frequency to the motor. To enable the
Run key on the digital operator for jog
input, set the value 01 (terminal mode)
in
(Run command source).
The type of deceleration used to end a motor jog operation is selectable by
programming function
. The options are:
•
valid during operation, Free-run stop (coasting)
•
valid during operation, Deceleration (normal level) and stop
•
valid during operation, Use DC braking and stop
•
invalid during operation, Free-run stop (coasting)
•
invalid during operation, Deceleration (normal level) and stop
•
invalid during operation, Use DC braking and stop
Option
Code
Terminal
Symbol
Function Name
State
Description
JG
Jogging
ON
Inverter is in Run Mode, output to motor runs at jog
parameter frequency
OFF
Inverter is in Stop Mode
Valid for inputs:
~
Example (requires input configuration
—see
page 3-85
):
See I/O specs on
page 4
–6
.
Required settings
=
,
>
,
>0,
Notes:
No jogging operation is performed when the set
value of jogging frequency
is smaller than
the start frequency
, or the value is 0Hz.
Be sure to stop the motor when switching the
function [JG] ON or OFF.
[JG]
1
0
[FW],
[RV]
1
0
Jog
speed
Jog decel type
JG
FW
7
6
5
4
3
2
1
L
P24
PLC
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......