Output Terminal Configuration
The inverter provides configuration for logic (discrete) and analog outputs, shown in the
table below.
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Initial data
Units
Output [11] function
[EDM assignable]
48 programmable functions
available for logic (discrete)
outputs
(see next section)
48 programmable functions available
for logic (discrete) outputs
(see next section)
13 programmable functions:
Output frequency (PWM)
Output current (PWM)
Output torque (PWM)
Output frequency (Pulse
train)
Output voltage (PWM)
Input power (PWM)
Electronic thermal load ratio
(PWM)
LAD frequency (PWM)
Output current (Pulse train)
Heat sink temperature
(PWM)
General output (PWM)
Pulse train input monitor
Option(PWM)
11 programmable functions:
Output frequency
Output current
Output torque
Output voltage
Input power
Electronic thermal load ratio
LAD frequency
Heat sink temperature
Output torque (with code)
General output
Option
Current with digital current
monitor output at 1,440Hz
Range is 20%~200% of rated
current
Select logic conversion, two option
codes:
normally open [NO]
normally closed [NC]
00
[RUN]
Output [12] function
01
[FA1]
Alarm relay function
05
[AL]
[EO] terminal selection
(Pulse/PWM output)
07
[AM] terminal selection
(Analog voltage output
0...10V)
07
[LAD]
Digital current monitor
reference value
Rated current
A
Pulse train input/output
scale conversion
If EO terminal is configured as
pulse train input (C027=15), scale
conversion is set in C047.
Pulse-out = Pulse-in
(C047)
Set range is 0.01 to 99.99
1.00
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......