B
26
Modbus Holding Registers
The following tables list the holding registers for the inverter interface to the network.
The table legend is given below.
Function Code - The inverter’s reference code for the parameter or function (same as
inverter keypad display)
Name - The standard functional name of the parameter or function for the inverter
R/W - The read-only(R) or read-write access(R/W) permitted to the data in the
inverter
Description - How the parameter or setting works (same as Chapter 3 description).
Reg. - The network
register address offset
for the value. Some values have a
high-byte and low-byte address.
Range - The numerical range for the network value that is sent and/or received
TIP: The network values are binary integers. Since these values cannot have an
embedded decimal point, for many parameters it represents the actual value (in
engineering units) multiplied by a factor of 10 or 100. Network communications must
use the listed range for network data. The inverter automatically divides received
values by the appropriate factor in order to establish the decimal point for internal use.
Likewise, the network host computer must apply the same factor when it needs to work
in engineering units. However, when sending data to the inverter, the network host
computer must scale values to the integer range listed for network communications.
Resolution - This is the quantity represented by the LSB of the network value, in
engineering units. When the network data range is greater than the inverter’s
internal data range, this 1-bit resolution will be fractional.
Register No.
Function name
Function code
R/W
Monitoring and setting items
Data
resolution
0000h
unused
-
-
Inaccessible
0001h
Frequency source
F001 (high)
R/W
0 to 40000 (valid when A001 = 03)
0.01 [Hz]
0002h
F001 (low)
R/W
0003h
Inverter status A
-
R
0: Initial status
2: Stopping
3: Running
4: Free-run stop
5: Jogging
6: DC braking
7: Retrying
8: Tripping
9: Undervoltage
(UV),
-
0004h
Inverter status B
-
R
0: Stopping, 1: Running, 2: Tripping
-
0005h
Inverter status C
-
R
0: ---
1: Stopping
2: Decelerating
3: Constant-speed
operation
4: Accelerating
5: Forward rotation
6: Reverse rotation
7: Switching from
fwd.
to rev. rotation,
8: Switching from
rev.
to fwd. rotation,
9: Starting fwd.
10: Starting rev.
-
0006h
PID feedback
-
R/W
0 to 10000
0.01 [%]
0007h
to
0010h
(Reserved)
-
R
-
-
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......