C
−
−
−
−
26
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
A B
Initial
data
Units
C102
Reset selection
Determines response to Reset
input [RS].
Four option codes:
00
…
Cancel trip state at input
signal ON transition, stops
inverter if in Run Mode
01
…
Cancel trip state at signal
OFF transition, stops inverter
if in Run Mode
02
…
Cancel trip state at input ON
transition, no effect if in Run
Mode
03
…
Clear the memories only
related to trip status
00
−
C103
Restart mode after reset
Determines the restart mode after
reset is given, three option codes:
00
…
Start with 0 Hz
01
…
Start with freq. matching
02
…
Start with active freq.
matching
00
-
C104
UP/DWN clear mode
Freq. set value when UDC signal is
given to the input terminal, two
option codes:
00
…
0 Hz
01
…
Original setting (in the
EEPROM memory at power
on)
00
-
C105
EO gain adjustment
Set range is 50 to 200%
100.
%
C106
AM gain adjustment
Set range is 50 to 200%
100.
%
C109
AM bias adjustment
Set range is 0 to 100%
0.
%
C111
Overload warning level 2 Sets the overload warning signal
level between 0% and 200% (from 0
to two time the rated current of the
inverter)
Rated
current
x 1.15
A
C130
Output [11] on delay
Set range is 0.0 to 100.0 sec.
0.0
Sec.
C131
Output [11] off delay
0.0
Sec.
C132
Output [12] on delay
Set range is 0.0 to 100.0 sec.
0.0
Sec.
C133
Output [12] off delay
0.0
Sec.
C140
Relay output on delay
Set range is 0.0 to 100.0 sec.
0.0
Sec.
C141
Relay output off delay
0.0
Sec.
C142
Logic output 1 operand A All the programmable functions
available for logic (discrete)
outputs except LOG1 to LOG3,
OPO, no
00
−
C143
Logic output 1 operand B
00
−
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......