Input Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description
OFF
Selects the direction of motor rotation: OFF = REV. While
the motor is rotating, a change of F/R will start a
deceleration, followed by a change in direction
PID
PID Disable
ON
Temporarily disables PID loop control. Inverter output turns
OFF as long as PID Enable is active (
=
)
OFF
Has no effect on PID loop operation, which operates
normally if PID Enable is active (
=
)
PIDC
PID Reset
ON
Resets the PID loop controller. The main consequence is that
the integrator sum is forced to zero
OFF
No effect on PID controller
UP
Remote Control UP
Function (motorized
speed pot.)
ON
Accelerates (increases output frequency) motor from current
frequency
OFF
Output to motor operates normally
DWN
Remote Control Down
Function (motorized
speed pot.)
ON
Decelerates (decreases output frequency) motor from current
frequency
OFF
Output to motor operates normally
UDC
Remote Control Data
Clearing
ON
Clears the UP/DWN frequency memory by forcing it to equal
the set frequency parameter F001. Setting
must be
set=
to enable this function to work
OFF
UP/DWN frequency memory is not changed
OPE
Operator Control
ON
Forces the source of the output frequency setting
and
the source of the Run command
to be from the digital
operator
OFF
Source of output frequency set by
and source of Run
command set by
is used
SF1
Multi-speed Select,
Bit operation Bit 1
ON
Bit encoded speed select, Bit 1, logical 1
OFF
Bit encoded speed select, Bit 1, logical 0
SF2
Multi-speed Select,
Bit operation Bit 2
ON
Bit encoded speed select, Bit 2, logical 1
OFF
Bit encoded speed select, Bit 2, logical 0
SF3
Multi-speed Select,
Bit operation Bit 3
ON
Bit encoded speed select, Bit 3, logical 1
OFF
Bit encoded speed select, Bit 3, logical 0
SF4
Multi-speed Select,
Bit operation Bit 4
ON
Bit encoded speed select, Bit 4, logical 1
OFF
Bit encoded speed select, Bit 4, logical 0
SF5
Multi-speed Select,
Bit operation Bit 5
ON
Bit encoded speed select, Bit 5, logical 1
OFF
Bit encoded speed select, Bit 5, logical 0
SF6
Multi-speed Select,
Bit operation Bit 6
ON
Bit encoded speed select, Bit 6, logical 1
OFF
Bit encoded speed select, Bit 6, logical 0
SF7
Multi-speed Select,
Bit operation Bit 7
ON
Bit encoded speed select, Bit 7, logical 1
OFF
Bit encoded speed select, Bit 7, logical 0
OLR
Overload Restriction
Source Changeover
ON
Perform overload restriction
OFF
Normal operation
TL
Torque Limit Selection
ON
Setting of
is enabled
OFF
Max. torque is limited with 200%
TRQ1
Torque limit switch 1
ON
Torque limit related parameters of Powering/regen, and
FW/RV modes are selected by the combinations of these
inputs.
OFF
TRQ2
Torque limit switch 2
ON
OFF
Input Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description
BOK
Brake confirmation
ON
Brake wait time (
) is valid
OFF
Brake wait time (
) is not valid
LAC
LAD cancellation
ON
Set ramp times are ignored. Inverter output immediately
follows the freq. command.
OFF
Accel. and/or decel. is according to the set ramp time
PCLR
Pulse counter clear
ON
Clear the position deviation data
OFF
Maintain the position deviation data
ADD
ADD frequency enable
ON
Adds the
(add frequency) value to the output frequency
OFF
Does not add the
value to the output frequency
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......