3
96
Electronic Thermal Warning Output
–
Please refer to page 3-48 for detailed information.
Zero speed detection Output
–
The inverter outputs the 0Hz speed detection signal
when the inverter output frequency falls below the threshold frequency specified in the
zero speed detection level (
).
To use this function, assign parameter “
” to one of the intelligent output terminals
[11] to [12] (
to
), or to the alarm relay output terminal (
).
This function applies to the inverter output frequency when the V/F characteristic
curve selection is based on the constant torque (VC), reduced torque (VP), free-V/F,
sensorless vector control. or 0Hz range sensorless vector control.
Heat Sink Overheat Warning Output
–
The inverter monitors the temperature of its
heat sink, and outputs the heat sink overheat warning (OHF) signal when the
temperature exceeds the heat sink overheat warning level specified in parameter
.
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Initial data
Units
Output mode of overload
warning
Two option codes:
During accel., decel. and
constant speed
During constant speed only
01
Overload warning level
Sets the overload warning signal
level between 0% and 200% (from
0 to two time the rated current of
the inverter)
Rated current
x 1.15
Overload warning level,
2
nd
motor
Sets the overload warning signal
level between 0% and 200% (from
0 to two time the rated current of
the inverter)
Rated current
x 1.15
Frequency arrival setting
for acceleration
Sets the frequency arrival setting
threshold for the output frequency
during acceleration,
range is 0.0 to 400.0 Hz
0.0
Frequency arrival setting
for deceleration
Sets the frequency arrival setting
threshold for the output frequency
during deceleration,
range is 0.0 to 400.0 Hz
0.0
PID deviation level
Sets the allowable PID loop error
magnitude (absolute value),
SP-PV, range is 0.0 to 100%
3.0
Frequency arrival setting
2 for acceleration
Set range is 0.0 to 400.0 Hz
0.00
Frequency arrival setting
2 for deceleration
Set range is 0.0 to 400.0 Hz
0.00
PID FBV output
high limit
When the PV exceeds this value,
the PID loop turns OFF the PID
second stage output, range is 0.0
to 100%
100.0
%
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......