4
90
Analog Output Operation
In inverter applications it is useful to monitor the
inverter operation from a remote location or from the
front panel of an inverter enclosure. In some cases,
this requires only a panel-mounted volt meter. In
other cases, a controller such as a PLC may provide
the inverter’s frequency command, and require
inverter feedback data (such as output frequency or
output current) to confirm actual operation. The
analog output terminal [AM] serves these purposes.
The inverter provides an analog voltage output on terminal [AM] with terminal [L] as
analog GND reference. The [AM] can output inverter frequency or current output value.
Note that the voltage range is 0 to +10V (positive-going only), regardless of forward or
reverse motor rotation. Use
to configure terminal [AM] as indicated below.
Func.
Code
Description
Inverter output frequency
Inverter output current
Inverter output torque
Digital output freqnency
Inverter output goltage
Inverter input power
Electronic Thermal Load
LAD frequency
Digital current monitor
Cooling fin temperature
General purpose
Pulse train
Option
AM H O OI L
+
-
A GND
Analog
Voltage
Output
10VDC
full scale,
2mA max
See I/O specs on page4-6
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......