B
24
Modbus Data Listing
Modbus Coil List
The following tables list the primary coils for the inverter interface to the network. The
table legend is given below.
Coil Number - The network
register address offset
for the coil. The coil data is a
single bit (binary) value.
Name - The functional name of the coil
R/W - The read-only (R) or read-write (R/W) access permitted to the inverter data
Description - The meaning of each of the states of the coils
Coil
No.
Item
R/W
Setting
0000h
unused
-
(Inaccessible)
0001h
Operation command
R/W
1: Run, 0: Stop (valid when A002 = 03)
0002h
Rotation direction command
R/W
1: Reverse rotation, 0: Forward rotation (valid when A002 = 03)
0003h
External trip (EXT)
R/W
1: Trip
0004h
Trip reset (RS)
R/W
1: Reset
0005h
(Reserved)
-
-
0006h
(Reserved)
-
-
0007h
Intelligent input terminal [1]
R/W
1: ON, 0: OFF (*1)
0008h
Intelligent input terminal [2]
R/W
1: ON, 0: OFF (*1)
0009h
Intelligent input terminal [3]
R/W
1: ON, 0: OFF (*1)
000Ah
Intelligent input terminal [4]
R/W
1: ON, 0: OFF (*1)
000Bh
Intelligent input terminal [5]
R/W
1: ON, 0: OFF (*1)
000Ch
Intelligent input terminal [6]
R/W
1: ON, 0: OFF (*1)
000Dh
Intelligent input terminal [7]
R/W
1: ON, 0: OFF (*1)
000Eh
(Reserved)
-
-
000Fh
Operation status
R
1: Run, 0: Stop (interlocked to "d003")
0010h
Rotation direction
R
1: Reverse rotation, 0: Forward rotation (interlocked to "d003")
0011h
Inverter ready
R
1: Ready, 0: Not ready
0012h
(Reserved)
-
-
0013h
RUN (running)
R
1: Tripping, 0: Normal
0014h
FA1 (constant-speed reached)
R
1: ON, 0: OFF
0015h
FA2 (set frequency overreached)
R
1: ON, 0: OFF
0016h
OL (overload advance notice (1))
R
1: ON, 0: OFF
0017h
OD (output deviation for PID
control)
R
1: ON, 0: OFF
0018h
AL (alarm signal)
R
1: ON, 0: OFF
0019h
FA3 (set frequency reached)
R
1: ON, 0: OFF
001Ah
OTQ (over-torque)
R
1: ON, 0: OFF
001Bh
(Reserved)
-
-
001Ch
UV (undervoltage)
R
1: ON, 0: OFF
001Dh
TRQ (torque limited)
R
1: ON, 0: OFF
001Eh
RNT (operation time over)
R
1: ON, 0: OFF
001Fh
ONT (plug-in time over)
R
1: ON, 0: OFF
0020h
THM (thermal alarm signal)
R
1: ON, 0: OFF
0021h
(Reserved)
-
-
0022h
(Reserved)
-
-
0023h
(Reserved)
-
-
0024h
(Reserved)
-
-
0025h
(Reserved)
-
-
0026h
BRK (brake release)
R
1: ON, 0: OFF
0027h
BER (brake error)
R
1: ON, 0: OFF
0028h
ZS (0 Hz detection signal)
R
1: ON, 0: OFF
0029h
DSE (speed deviation maximum)
R
1: ON, 0: OFF
002Ah
POK (positioning completed)
R
1: ON, 0: OFF
002Bh
FA4 (set frequency overreached 2)
R
1: ON, 0: OFF
002Ch
FA5 (set frequency reached 2)
R
1: ON, 0: OFF
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......