Starting Contact Signal
The inverter gives out the starting contact signal (FR) while it is receiving an
operational command. The FR signal is given out, regardless the setting of the run
command source setting (
). If the forward operation (FW) and reverse operation
(RV) are given at the same time, the inverter stops the motor operation.
Option
Code
Terminal
Symbol
Function Name
State
Description
FR
Starting contact
signal
ON
Either FW or RV is given, or no operation command
is given
OFF
Both FW and RV is given at the same time
Valid for inputs:
11, 12, AL0
– AL2
Example for terminal [11] (default output
configuration shown
– see
page 3-89
):
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration
– see
page 4-51 and 3-91
):
See I/O specs on
page 4-6
Required settings
Notes:
Forward operation command
Reverse operation command
Starting contact signal (FR)
RY
Inverter output
terminal circuit
CM2
11
FR
AL1
Power
supply
Load
AL0
AL2
Inverter logic
circuit board
FR