Ver.2
49
Standard Functions
NOTE:. Mark “
” in A line of [ Run Mode Edit] shows the accessible parameters when b031 is not set “10”,
high level access.
NOTE:. Mark “
” in B line of [ Run Mode Edit] shows the accessible parameters when b031 is set “10”,
high level access
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
A
B
Initial data
Units
Frequency source
Eight options; select codes:
POT on ext. operator
Control terminal
Function F001 setting
Modbus network input
Option
Pulse train input
via EzSQ
Calculate function output
01
Frequency source,
2
nd
motor
01
Run command source
Four options; select codes:
Control terminal
Run key on keypad,
or digital operator
Modbus network input
Option
01
Run command source,
2
nd
motor
01
Base frequency
Settable from 30 Hz to the maximum
frequency(
)
50.0
Hz
Base frequency,
2
nd
motor
Settable from 30 Hz to the 2
nd
maximum
frequency(
)
50.0
Hz
Maximum frequency
Settable from the base
frequency to 400 Hz
50.0
Hz
Maximum frequency,
2
nd
motor
Settable from the 2
nd
base
frequency to 400 Hz
50.0
Hz
[AT] selection
Three options; select codes:
...Select between [O] and [OI] at [AT]
(ON=OI, OFF=O)
...Select between [O] and external POT
at [AT]
(ON=POT, OFF=O)
...Select between [OI] and external
POT at [AT]
(ON=POT, OFF=OI)
00
[O] input active range start
frequency
The output frequency corresponding to
the analog input range starting point,
range is 0.00 to 400.0
0.00
Hz
[O] input active range end
frequency
The output frequency corresponding to
the analog input range ending point,
range is 0.0 to 400.0
0.00
Hz
[O] input active range start
voltage
The starting point (offset) for the active
analog input range,
range is 0. to 100.
0.
%
[O] input active range end
voltage
The ending point (offset) for the active
analog input range,
range is 0. to 100.
100.
%
[O] input start frequency
enable
Two options; select codes:
Use offset (
value)
Use 0Hz
01
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......