No.
Function name
Function
code
R/W
Monitoring and setting items
Data
resolution
1415h Output [11] function
C021
R/W
0 (RUN: running), 1 (FA1: constant-speed reached), 2 (FA2: set
frequency overreached), 3 (OL: overload notice advance signal
(1)), 4 (OD: output deviation for PID control), 5 (AL: alarm signal),
6 (FA3: set frequency reached), 7 (OTQ: over-torque), 9 (UV:
undervoltage), 10 (TRQ: torque limited), 11 (RNT: operation time
over), 12 (ONT: plug-in time over), 13 (THM: thermal alarm
signal), 19 (BRK: brake release), 20 (BER: braking error), 21 (ZS:
0 Hz detection signal), 22 (DSE: speed deviation maximum), 23
(POK: positioning completed), 24 (FA4: set frequency
overreached 2), 25 (FA5: set frequency reached 2), 26 (OL2:
overload notice advance signal (2)), 31 (FBV: PID feedback
comparison), 32 (NDc: communication line disconnection), 33
(LOG1: logical operation result 1), 34 (LOG2: logical operation
result 2), 35 (LOG3: logical operation result 3), 39 (WAC:
capacitor life warning), 40 (WAF: cooling-fan), 41 (FR: starting
contact signal), 42 (OHF: heat sink overheat warning), 43 (LOC:
low-current indication signal), 44 (M01: general-purpose output 1),
45 (M02: general-purpose output 2), 46 (M03: general-purpose
output 3), 50 (IRDY: inverter ready), 51 (FWR: forward rotation),
52 (RVR: reverse rotation), 53 (MJA: major failur)
54 (WCO: window comparator O), 55 (WCO: window comparator
OI), 58(FREF),59(REF),60(SETM),62(EDM),63(OPO:Option)
-
1416h Output [12] function
C022
R/W
-
1421h to
1423h
(Reserved)
-
-
-
141Ah Alarm relay function
C026
R/W
-
141Bh [EO] terminal selection
C027
R/W
0 (output frequency), 1 (output current), 2 (output torque), 3
(digital output frequency), 4 (output voltage), 5 (input power), 6
(electronic thermal overload), 7 (LAD frequency), 8 (digital current
monitoring), 10 (heat sink temperature), 12 (general-purpose
output YA0),15 ,16(option)
-
141Ch [AM] terminal selection
C028
R/W
0 (output frequency), 1 (output current), 2 (output torque), 4
(output voltage), 5 (input power), 6 (electronic thermal overload), 7
(LAD frequency), 10 (heat sink temperature), 11 (output torque
[signed value]), 13 (general-purpose output YA1),16(option)
-
141Dh (reserved)
-
-
-
-
141Eh
Digital current monitor
reference value
C030
R/W 200 to 2000
0.1 [%]
141Fh Output [11] active state
C031
R/W 0 (NO), 1 (NC)
-
1420h Output [12] active state
C032
R/W 0 (NO), 1 (NC)
-
1421h to
1423h
(Reserved)
-
-
-
-
1424h Alarm relay active state
C036
R/W 0 (NO), 1 (NC)
-
1425h (Reserved)
-
-
-
-
1426h
Output mode of low current
detection
C038
R/W
0 (output during acceleration/deceleration and constant-speed
operation), 1 (output only during constant-speed operation)
-
1427h Low current detection level
C039
R/W 0 to 2000
0.1 [%]
1428h Overload signal output mode
C040
R/W
00 (output during acceleration/deceleration and constant-speed
operation), 01 (output only during constant-speed operation)
-
1429h Overload warning level
C041
R/W 0 to 2000
0.1 [%]
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......