Ver.2
64
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
A
B
Initial data
Units
[AM] terminal selection
(Analog voltage output
0...10V)
11 programmable functions:
Output frequency
Output current
Output torque
Output voltage
Input power
Electronic thermal load ratio
LAD frequency
Heat sink temperature
Output torque (with code)
General output
Option
07
[LAD]
Digital current monitor
reference value
Current with digital current monitor
output at 1,440Hz
Range is 20%~200% of rated current
Rated
current
A
Output [11] active state
Select logic conversion, two option codes:
normally open [NO]
normally closed [NC]
00
Output [12] active state
00
Alarm relay active state
01
Output mode of low current
detection
Two option codes:
During acceleration, deceleration
and constant speed
During constant speed only
01
Low current detection level
Set the level of low load detection, range
is 0.0 to 2.0*inverter rated current
INV rated
current
A
Output mode of overload
warning
Two option codes:
During accel., decel. and constant
speed
During constant speed only
01
Overload warning level
Sets the overload warning signal level
between 0% and 200% (from 0 to two time
the rated current of the inverter)
Rated
current
x 1.15
A
Overload warning level, 2
nd
motor
Sets the overload warning signal level
between 0% and 200% (from 0 to two time
the rated current of the inverter)
Rated
current
x 1.15
A
Frequency arrival setting for
acceleration
Sets the frequency arrival setting
threshold for the output frequency during
acceleration,
range is 0.0 to 400.0 Hz
0.00
Hz
Frequency arrival setting for
deceleration
Sets the frequency arrival setting
threshold for the output frequency during
deceleration,
range is 0.0 to 400.0 Hz
0.00
Hz
PID deviation level
Sets the allowable PID loop error
magnitude (absolute value), SP-PV, range
is 0.0 to 100%
3.0
%
Frequency arrival setting 2
for acceleration
Set range is 0.0 to 400.0 Hz
0.00
Hz
Frequency arrival setting 2
for deceleration
Set range is 0.0 to 400.0 Hz
0.00
Hz
Pulse train input/output
scale conversion
If EO terminal is configured as pulse
train input (C027=15), scale conversion is
set in C047.
Pulse-out = Pulse-in
(C047)
Set range is 0.01 to 99.99
1.00
PID FBV output
high limit
When the PV exceeds this value, the PID
loop turns OFF the PID second stage
output, range is 0.0 to 100%
100.0
%
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......