Ver.3
−
−
−
−
57
Case 2: When selecting 32-bit parameter for an internal register. (Please refer to the page 1 for setting
range.
Reading Holding Register [03h] , Target register = external register
Query:
Response:
No
Field Name
Example
(Hex)
1
Slave address
01
2
Function code
83
3
Exception code
31
4
CRC-16 (high order)
80
5
CRC-16 (low order)
E4
Only 16-bit Holding register can be designated as an internal register. So You will get an exception
response if you choose 32-bit register for an internal register.
No
Field Name
Example
(Hex)
1
Slave address
01
2
Function code
03
3
Register start address (high order)
60
4
Register start address (low order)
01
5
Number of holding registers (high order)
00
6
Number of holding registers (low order)
01
7
CRC-16 (high order)
CB
8
CRC-16 (low order)
CA
Register address value = Register
Number - 1
One register