Ver.3
−
−
−
−
19
(1)
Subtraction function of electronic thermal for motor
Electronic thermal protection selection parameter (b910) is prepared to be able to select from 3
patterns. When b090=0 is set, subtraction is invalid and identical to function before Ver.3.0.
①
when b910 = 01
when output current is less than thermal count level, subtracted constantly with fixed rate as
max value thermal counter (trip level) down to 0 in 10 minutes.
Fig.1 Thermal Counter subtraction image when
b910=01
Output Current
Thermal Count
llevel
Thermal Counter
100[%]
(Trip Level)
Trip
10[min]
Output Current
Thermal Counter
Rate to subtract
100%/10min