Ensure Adequate Ventilation
Step 2: To summarize the caution messages – you will need to find a solid,
non-flammable, vertical surface that is in a relatively clean and dry environment. In
order to ensure enough room for air circulation around the inverter to aid in cooling, it
is recommended to maintain the specified clearance and the inverter specified in the
below diagram.
CAUTION: Be sure to maintain the specified clearance area around the inverter and to
provide adequate ventilation. Otherwise, the inverter may overheat and cause
equipment damage or fire.
Keep Debris Out of Inverter Vents
Step 3: Before proceeding to the wiring section, it’s
a good time to
temporarily
covers the inverter’s
ventilation openings. Paper and masking tape are
all that is needed. This will prevent harmful debris
such as wire clippings and metal shavings from
entering the inverter during installation.
Please observe this checklist while mounting the
inverter:
1.
The ambient temperature must be in the range
of
10 to 50
C.
2.
Keep any other heat-producing equipment as
far away from the inverter as possible.
3.
When installing the inverter in an enclosure, maintain the clearance around the
inverter and verify that its ambient is within specification when the enclosure door
is closed.
4.
Do not remove the front housing at any time during operation.
2
3
Air flow
10 cm (3.94
”)
minimum
10 cm (3.94
”)
minimum
5 cm (1.97
”)
minimum
5 cm (1.97
”)
minimum
Clear area
WJ200
inverter
Ventilation holes (top)
Ventilation holes
(both sides)
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......