Output Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description
RUN
Run Signal
ON
When the inverter is in Run Mode
OFF
When the inverter is in Stop Mode
FA1
Frequency Arrival
Type 1–Constant
Speed
ON
When output to motor is at the set frequency
OFF
When output to motor is OFF, or in any acceleration or
deceleration ramp
FA2
Frequency Arrival
Type 2–Over frequency ON
When output to motor is at or above the set freq., even if in
accel (
) or decel (
) ramps
OFF
When output to motor is OFF, or at a level below the set
frequency
OL
Overload Advance
Notice Signal 1
ON
When output current is more than the set threshold (
) for
the overload signal
OFF
When output current is less than the set threshold for the
deviation signal
OD
Output Deviation for
PID Control
ON
When PID error is more than the set threshold for the
deviation signal
OFF
When PID error is less than the set threshold for the
deviation signal
AL
Alarm Signal
ON
When an alarm signal has occurred and has not been cleared
OFF
When no alarm has occurred since the last cleaning of
alarm(s)
FA3
Frequency Arrival
Type 3–Set frequency
ON
When output to motor is at the set frequency, during accel
(
) and decel (
).
OFF
When output to motor is OFF, or is not at a level of the set
frequency
OTQ
Over/under Torque
Signal
ON
Estimated motor torque exceeds the specified level
OFF
Estimated motor torque is lower than the specified level
UV
Undervoltage
ON
Inverter is in Undervoltage
OFF
Inverter is not in Undervoltage
TRQ
Torque Limited Signal ON
Torque limit function is executing
OFF
Torque limit function is not executing
RNT
Run Time Expired
ON
Total running time of the inverter exceeds the specified value
OFF
Total running time of the inverter does not exceed the
specified value
ONT
Power ON time
Expired
ON
Total power ON time of the inverter exceeds the specified
value
OFF
Total power ON time of the inverter does not exceed the
specified value
THM
Thermal Warning
ON
Accumulated thermal count exceeds the
set value
OFF
Accumulated thermal count does not exceed the
set
value
BRK
Brake Release Signal
ON
Output for brake release
OFF
No action for brake
BER
Brake Error Signal
ON
Brake error has occurred
OFF
Brake performance is normal
ZS
Zero Hz Speed
Detection Signal
ON
Output frequency falls below the threshold specified in
OFF
Output frequency is higher than the threshold specified in
DSE
Speed Deviation
Excessive
ON
Deviation of speed command and actual speed exceeds the
specified value
.
OFF
Deviation of speed command and actual speed does not exceed
the specified value
.
POK
Positioning Completion ON
Positioning is completed
OFF
Positioning is not completed
FA4
Frequency Arrival
Type 4–Over frequency ON
When output to motor is at or above the set freq., even if in
accel (
) or decel (
) ramps
OFF
When output to motor is OFF, or at a level below the set
frequency
FA5
Frequency Arrival
Type 5–Set frequency
ON
When output to motor is at the set frequency, during accel
(
) and decel (
).
OFF
When output to motor is OFF, or is not at a level of the set
frequency
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......