Ver.3
−
−
−
−
60
Ex 9
Ex 9
Ex 9
Ex 9 A case where an external register is invalid (An external register number is linked together to two or
more different internal register number.)
*
**
*Below setting must be entered from the operator before Modbus communication, with power cycle.
External register
number
Internal register
number
Scaling
Format
6001h
120F
h(
A013
)
1.000
Unsigned
6001h
1210h
(
A014
)
1.000
Unsigned
(1)
Reading Holding Register [03h]
、
Target register = external register
Query:
Response:
No
Field Name
Example
(Hex)
1
Slave address
01
2
Function code
83
3
Exception code
31
4
CRC-16 (high order)
80
5
CRC-16 (low order)
E4
No
Field Name
Example
(Hex)
1
Slave address
01
2
Function code
03
3
Register start address (high
order)
60
4
Register start address (low
order)
00
5
Number of holding registers
(high order)
00
6
Number of holding registers
(low order)
01
7
CRC-16 (high order)
9A
8
CRC-16 (low order)
0A
Register address value = Register
Number - 1
One register