Miscellaneous Functions
The following table contains miscellaneous functions not in other function groups.
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Initial data
Units
Debug mode enable *
Displays debug parameters.
Two option codes:
Disable
Enable <Do not set>
(for factory use)
00
Up/Down memory mode
selection
Controls speed setpoint for the
inverter after power cycle.
Two option codes:
Clear last frequency (return
to default frequency
)
Keep last frequency adjusted
by UP/DWN
00
Reset selection
Determines response to Reset
input [RS].
Four option codes:
Cancel trip state at input
signal ON transition, stops
inverter if in Run Mode
Cancel trip state at signal
OFF transition, stops inverter
if in Run Mode
Cancel trip state at input ON
transition, no effect if in Run
Mode
Clear the memories only
related to trip status
00
Restart mode after reset
Determines the restart mode after
reset is given, three option codes:
Start with 0 Hz
Start with freq. matching
Start with active freq.
matching
00
UP/DWN clear mode
Freq. set value when UDC signal
is given to the input terminal, two
option codes:
0 Hz
Original setting (in the
EEPROM memory at power
on)
00
CAUTION: Do not change the debug mode for safety reasons. Otherwise unexpected
performances may occur.
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......