3
71
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Initial data
Units
Cooling fan control
Selects when the fan is ON during
inverter operation, three options:
Fan is always ON
Fan is ON during run, OFF
during stop (5 minute delay
from ON to OFF)
Fan is temperature controlled
01
Clear elapsed time of
cooling fan
Two option codes:
Count
Clear
00
Initialization target data
Select initialized parameters, four
option codes:
All parameters
All parameters except
in/output terminals and
communication.
Only registered parameters in
xxx.
All parameters except
registered parameters in
xxx
and
.
00
Dynamic braking control
(BRD) selection
Three option codes:
Disable
Enable during run only
Enable always
00
BRD activation level
Range is:
330 to 380V (200V class)
660 to 760V (400V class)
360/
720
V
Initialization trigger
(*)
This is to perform initialization by
parameter input with
,
and
. Two option codes:
Initialization disable
Perform initialization
00
(*) Note: When 01 is set on b180, and SET key is pressed, initialization starts
immediately and there is not any way to restore the previous parameter setting. WJ200
doesn’t have a method to trigger the initialization by key action as the other Hitachi
inverter models have.
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......