C
−
−
−
−
10
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
A B Initial data
Units
A097
Acceleration curve selection
Set the characteristic curve of
Acc1 and Acc2, five options:
00
…
linear
01
…
S-curve
02
…
U-curve
03
…
Inverse U-curve
04
…
EL S-curve
01
−
A098
Deceleration curve selection
Set the characteristic curve of
Dec1 and Dec2, options are
same as above (
a097
)
01
−
A101
[OI] input active range start
frequency
The output frequency
corresponding to the analog
input range starting point,
range is 0.0 to 400.0 Hz
0.00
Hz
A102
[OI] input active range end
frequency
The output frequency
corresponding to the current
input range ending point,
range is 0.0 to 400.0 Hz
0.00
Hz
A103
[OI] input active range start
current
The starting point (offset) for
the current input range,
range is 0. to 100.%
20.
%
A104
[OI] input active range end
current
The ending point (offset) for the
current input range,
range is 0. to 100.%
100.
%
A105
[OI] input start frequency
select
Two options; select codes:
00
…
Use offset (
A101
value)
01
…
Use 0Hz
00
−
a131
Acceleration curve constant
Range is 01 to 10.
02
−
a132
Deceleration curve constant
Range is 01 to 10.
02
−
A141
A input select for calculate
function
Seven options:
00
…
Operator
01
…
VR
02
…
Terminal [O] input
03
…
Terminal [OI] input
04
…
RS485
05
…
Option
07
…
Pulse train input
02
−
A142
B input select for calculate
function
Seven options:
00
…
Operator
01
…
VR
02
…
Terminal [O] input
03
…
Terminal [OI] input
04
…
RS485
05
…
Option
07
…
Pulse train input
03
−
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......