Ver.2
55
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
A
B
Initial data
Units
Curvature of EL-S-curve at
the end of deceleration
Range is 0 to 50%
10.
%
Deceleration hold frequency
Sets the frequency to hold deceleration,
range is 0.0 to 400.0Hz
0.00
Hz
Deceleration hold time
Sets the duration of deceleration hold,
range is 0.0 to 60.0 seconds.
0.0
s
PID sleep function action
threshold
Sets the threshold for the action, set
range 0.0 to 400.0 Hz
0.00
Hz
PID sleep function action
delay time
Sets the delay time for the action, set
range 0.0 to 25.5 seconds.
0.0
s
[VR] input active range start
frequency
The output frequency corresponding to
the analog input range starting point,
range is 0.0 to 400.0 Hz
0.00
Hz
[VR] input active range end
frequency
The output frequency corresponding to
the current input range ending point,
range is 0.0 to 400.0 Hz
0.00
Hz
[VR] input active range
start %
The starting point (offset) for the current
input range,
range is 0. to 100.%
0.
%
[VR] input active range
end %
The ending point (offset) for the current
input range,
range is 0. to 100.%
100.
%
[VR] input start frequency
select
Two options; select codes:
Use offset (
value)
Use 0Hz
01
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......