Terminal Name
Description
Ratings
L (in bottom row) *2
GND for analog signals
Sum of [OI], [O], and [H] currents (return)
OI
Analog current input
4 to 19.6 mA range, 20 mA nominal,
input impedance 250
O
Analog voltage input
0 to 9.8 VDC range, 10 VDC nominal,
input impedance 10 k
H
+10V analog reference
10VDC nominal, 10mA max.
SP, SN
Serial communication terminal For RS485 Modbus communication.
AL0
Relay common contact
250VAC,
2.5A (R load) max.
250VAC,
0.2A (I load, P.F.=0.4) max.
100VAC, 10mA min.
30VDC,
3.0A (R load) max.
30VDC,
0.7A (I load, P.F.=0.4) max.
5VDC, 100mA min.
AL1 *3
Relay contact, normally open
AL2 *3
Relay contact, normally closed
Note 1: The two terminals [L] are electrically connected together inside the inverter.
Note 2: We recommend using [L] logic GND (to the right) for logic input circuits and
[L] analog GND (to the left) for analog I/O circuits.
Note 3: Default relay N.O./N.C. configuration is reversed. See
page 4-60
.
Wiring sample of control logic terminal (sink logic)
Note:
If relay is connected to intelligent output, install a diode across the relay coil
(reverse-biased) in order to suppress the turn-off spike.
Caution for intelligent terminals setting
In turning on power when the input to the intelligent terminals become the following operations,
the set data might be initialized.
Please ensure not becoming the following operations, in changing the function allocation
of the intelligent input terminal.
SP
EO
EA
H
O
OI
L
AM
CM2
12 11/EDM
Freq. meter
Variable
resistor
for freq. setting
(1k
-2k
)
Jumper wire
(source logic)
RY
SN
7/EB
6
5/PTC 4/GS2 3/GS1
2
1
L
PLC
P24
RY
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......