Pulse Train Input Operation
The WJ200 inverter is capable of accepting pulse train input signals, that are used for
frequency command, process variable (feedback) for PID control, and simple positioning.
The dedicated terminal is called “EA” and “EB”. Terminal “EA” is a dedicated terminal,
and the terminal “EB” is an intelligent terminal, that has to be changed by a
parameter setting.
Terminal Name
Description
Ratings
EA
Pulse train input A
For frequency command, 32kHz max.
Common is [L]
EB
(Input terminal 7)
Pulse train input B
(Set
to
)
27Vdc max.
For frequency command, 2kHz max.
Common is [PLC]
(1) Frequency Command by pulse train input
When using this mode, you should set
to
. In this case the frequency is detected
by input-capture, and calculated based on the ratio of designated max. frequency
(under 32kHz). Only an input terminal “EA” will be used in this case.
(2) Using for process variable of PID control
You can use the pulse train input for process variable (feedback) of PID control. In this
case you need to set
to
. Only “EA” input terminal is to be used.
(3) Simple positioning by pulse train input
This is to use the pulse train input like an encoder signal. You can select three types of
operation.
Analog
output
Logic input
Logic
output
Jumper wire
PLC
Analog
input
Pulse
input
Pulse
Train
output
RS485
comm.
RS485
comm.
P24
1 L
3 2
5 4
6
SN 7
12 11
AM
CM2
OI L
H O
EA
SP EO
AL2
AL1
AL0
Relay contact
Train
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......