Ver.2
72
Output Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description
OL2
Overload Advance
Notice Signal 2
ON
When output current is more than the set threshold (
) for
the overload signal
OFF
When output current is less than the set threshold for the
deviation signal
ODc
Analog Voltage Input
Disconnect Detection
ON
When the [O] input value <
setting (signal loss detected)
OFF
When no signal loss is detected
OIDc
Analog Current input
Disconnect Detection
ON
When the [OI] input value <
setting (signal loss detected)
OFF
When no signal loss is detected
FBV
PID Second Stage
Output
ON
Transitions to ON when the inverter is in RUN Mode and the
PID Process Variable (PV) is less than the Feedback Low
Limit (
)
OFF
Transitions to OFF when the PID Process Variable (PV)
exceeds the PID High Limit (
), and transitions to OFF
when the inverter goes from Run Mode to Stop Mode
NDc
Network Disconnect
Detection
ON
When the communications watchdog timer (period specified
by
) has time out
OFF
When the communications watchdog timer is satisfied by
regular communications activity
LOG1
Logic Output Function
1
ON
When the Boolean operation specified by
has a logical “1”
result
OFF
When the Boolean operation specified by
has a logical “0”
result
LOG2
Logic Output Function
2
ON
When the Boolean operation specified by
has a logical “1”
result
OFF
When the Boolean operation specified by
has a logical “0”
result
LOG3
Logic Output Function
3
ON
When the Boolean operation specified by
has a logical “1”
result
OFF
When the Boolean operation specified by
has a logical “0”
result
WAC
Capacitor Life Warning
Signal
ON
Lifetime of internal capacitor has expired.
OFF
Lifetime of internal capacitor has not expired.
WAF
Cooling Fan Warning
Signal
ON
Lifetime of cooling fan has expired.
OFF
Lifetime of cooling fan has not expired.
FR
Starting Contact
Signal
ON
Either FW or RV command is given to the inverter
OFF
No FW or RV command is given to the inverter, or both are
given to the inverter
OHF
Heat Sink Overheat
Warning
ON
Temperature of the heat sink exceeds a specified value (
)
OFF
Temperature of the heat sink does not exceed a specified value
(
)
LOC
Low load detection
ON
Motor current is less than the specified value (
)
OFF
Motor current is not less than the specified value (
)
MO1
General Output 1
ON
General output 1 is ON
OFF
General output 1 is OFF
MO2
General Output 2
ON
General output 2 is ON
OFF
General output 2 is OFF
MO3
General Output 3
ON
General output 3 is ON
OFF
General output 3 is OFF
IRDY
Inverter Ready Signal
ON
Inverter can receive a run command
OFF
Inverter cannot receive a run command
FWR
Forward Rotation
ON
Inverter is driving the motor in forward direction
OFF
Inverter is not driving the motor in forward direction
RVR
Reverse Rotation
ON
Inverter is driving the motor in reverse direction
OFF
Inverter is not driving the motor in reverse direction
MJA
Major Failure Signal
ON
Inverter is tripping with major failure
OFF
Inverter is normal, or is not tripping with major failure
WCO
Window Comparator
for Analog Voltage
Input
ON
Analog voltage input value is inside of the window comparator
OFF
Analog voltage input value is outside of the window
comparator
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......