Power Wiring Access
–
First, ensure no power source is connected to the inverter. If
power has been connected, verify that the Power LED is OFF and then wait five
minutes after power down to proceed. After removing the terminal cover and front
housing cover, the housing partitions that cover the power and motor wiring exits will
be able to slide upward as shown below.
Notice the four wire exit slots in the housing partition. This helps keep the power and
motor wiring (to the left) separated from the signal-level logic or analog wiring (to the
right).
Remove the housing partition and as shown as set them aside in a secure place while
wiring. Be sure to replace them afterward. Never operate the inverter with the
partition removed or the front housing cover removed.
The power input and motor 3-phase wiring connect to the lower row of the terminals.
The upper row of power terminals connect to optional braking units or DC link choke.
The following section in this chapter will describe system design and guide you through
a step-by-step installation process. After the section on wiring, this chapter will show
how to use the front panel keys to access functions and edit parameters.
NOTE: The h
ousing partition can be removed without removing the front cover in
the following models.
Single-phase 200V: 0.7 to 2.2kW
Three-phase 200V: 1.5 to 15kW
Three-phase 400V: All size
Terminal cover
Front cover
Housing partition
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......