4
64
Running Time and Power On Time Over Signal
The inverter outputs the operation time expiration signal and power on time expiration
signal.
To enable this function, assign “
(RNT)”, and/or “
(ONT)” to intelligent output
terminals.
Option
Code
Terminal
Symbol
Function Name
State
Description
RNT
Run time expiration
signal
ON
Accumulated operation time of the inverter exceeds
the set value of
OFF
Accumulated operation time of the inverter does not
exceed the set value of
ONT
Power ON time
expiration signal
ON
Accumulated power on time of the inverter exceeds
the set value of
OFF
Accumulated power on time of the inverter does not
exceed the set value of
Valid for inputs:
11, 12, AL0
– AL2
Example for terminal [11] (default output
configuration shown
– see
page 3-89
):
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration
– see
page 4-51 and 3-91
):
See I/O specs on
page 4-6
Required settings
Notes:
The example circuit for terminal [11] drives a relay
coil. Note the use of a diode to prevent the
negative-going turn-off spike generated by the coil
from damaging the inverter’s output transistor.
RY
Inverter output
terminal circuit
CM2
11
RNT
AL1
Power
supply
Load
AL0
AL2
Inverter logic
circuit board
ONT
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......