Ver.2
51
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
A
B
Initial data
Units
V/f gain
Sets voltage gain of the inverter, range is
20. to 100.%
100.
%
V/f gain, 2
nd
motor
100.
%
Voltage compensation gain
for automatic torque boost
Sets voltage compensation gain under
automatic torque boost, range is 0. to
255.
100.
Voltage compensation gain
for automatic torque boost,
2
nd
motor
100.
Slip compensation gain for
automatic torque boost
Sets slip compensation gain under
automatic torque boost, range is 0. to
255.
100.
Slip compensation gain for
automatic torque boost,
2
nd
motor
100.
DC braking enable
Three options; select codes:
Disable
Enable during stop
Frequency detection
00
DC braking frequency
The frequency at which DC braking
begins,
range is from the start frequency (
)
to 60Hz
0.50
Hz
DC braking wait time
The delay from the end of controlled
deceleration to start of DC braking
(motor free runs until DC braking
begins),
range is 0.0 to 5.0 seconds.
0.0
s
DC braking force for
deceleration
Level of DC braking force, settable from
0 to 100%
50.
%
DC braking time for
deceleration
Sets the duration for DC braking, range
is from 0.0 to 60.0 seconds.
0.5
s
DC braking / edge or level
detection for [DB] input
Two options; select codes:
Edge detection
Level detection
01
DC braking force at start
Level of DC braking force at start,
settable from 0 to 100%
0.
%
DC braking time at start
Sets the duration for DC braking, range
is from 0.0 to 60.0 seconds.
0.0
s
Carrier frequency during DC
braking
Carrier frequency of DC braking
performance, range is from 2.0 to
15.0kHz
5.0
kHz
Frequency upper limit
Sets a limit on output frequency less
than the maximum frequency (
).
Range is from frequency lower limit
(
) to maximum frequency (
).
0.0 setting is disabled
>0.0 setting is enabled
0.00
Hz
Frequency upper limit,
2nd motor
Sets a limit on output frequency less
than the maximum frequency (
).
Range is from frequency lower limit
(
) to maximum frequency (
).
0.0 setting is disabled
>0.0 setting is enabled
0.00
Hz
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......