Active Frequency Matching Restart
Goal of the active frequency matching is the same as normal frequency matching.
Difference is the method. Please select the suitable one for your application.
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Initial data
Units
Current level of active freq.
matching
Sets the current level of active freq.
matching restart, range is
0.1*inverter rated current to
2.0*inverter rated current,
resolution 0.1
Rated
current
A
Deceleration rate of active
freq. matching
Sets the deceleration rate when
active freq. matching restart, range
is 0.1 to 3000.0, resolution 0.1
0.5
sec.
Start freq. of active freq.
matching
Three option codes:
freq at previous shutoff
start from max. Hz
start from set frequency
00