4
62
Undervoltage Signal
The inverter outputs the undervoltage signal when it detects that the inverter is in
undervoltage situation.
To enable this function, assign “
(UV)” to an intelligent output terminal.
Option
Code
Terminal
Symbol
Function Name
State
Description
UV
Undervoltage signal
ON
Inverter is in undervoltage
OFF
Inverter is in normal condition
Valid for inputs:
11, 12, AL0
– AL2
Example for terminal [11] (default output
configuration shown
– see
page 3-89
):
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration
– see
page 4-51 and 3-91
):
See I/O specs on
page 4-6
Required settings
Notes:
The example circuit for terminal [11] drives a relay
coil. Note the use of a diode to prevent the
negative-going turn-off spike generated by the coil
from damaging the inverter’s output transistor.
RY
Inverter output
terminal circuit
CM2
11
UV
AL1
Power
supply
Load
AL0
AL2
Inverter logic
circuit board
UV