4
65
Electronic Thermal Warning Signal Output
You can configure this function so that the inverter outputs a warning signal before the
electronic thermal protection operates against motor overheat. You can also set the
threshold level to output a warning signal with the electronic thermal warning level
setting (
).
To output the warning signal, assign function “
(THM)” to one of the intelligent
output terminals [11] to [12], or to the relay output terminal.
Option
Code
Terminal
Symbol
Function Name
State
Description
THM
Thermal warning
signal output
ON
Accumulated thermal level exceeds the electronic
thermal warning level (
)
OFF
Accumulated thermal level does not exceed the
electronic thermal warning level (
)
Valid for inputs:
11, 12, AL0
– AL2
Example for terminal [11] (default output
configuration shown
– see
page 3-89
):
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration
– see
page 4-51 and 3-91
):
See I/O specs on
page 4-6
Required settings
Notes:
The example circuit for terminal [11] drives a relay
coil. Note the use of a diode to prevent the
negative-going turn-off spike generated by the coil
from damaging the inverter’s output transistor.
RY
Inverter output
terminal circuit
CM2
11
THM
AL1
Power
supply
Load
AL0
AL2
Inverter logic
circuit board
THM
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......