30
Acceleration stop/Deceleration stop
–
The acceleration stop and deceleration stop
frequency setting allows you to make the inverter wait, upon starting the motor or upon
decelerating the motor, until the motor slip becomes less when the motor load causes a
large moment of inertia. Use this function if the inverter trips because of overcurrent
when starting or decelerating the motor. This function operates with every acceleration
and deceleration pattern, regardless the acceleration and deceleration curve selection
(
and
). Instead of setting
,
,
and
, acceleration and
deceleration can be held by intelligent input configured as "
:HLD".
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Initial data
Units
Acceleration hold frequency
Sets the frequency to hold
acceleration, range is 0.0 to
400.0Hz
Sets the duration of
acceleration hold, range is 0.0
to 60.0 seconds
0.00
Hz
Acceleration hold time
0.0
sec.
Deceleration hold frequency
Sets the frequency to hold
deceleration, range is 0.0 to
400.0Hz
0.0
Hz
Deceleration hold time
Sets the duration of
deceleration hold, range is 0.0
to 60.0 seconds
0.0
sec.
HLD input
Output frequency
t
Output frequency
t
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......