4
45
Analog Command Hold
This function allows you to make the inverter hold the analog command input via the
external analog input terminal when the AHD terminal is made ON.
While the AHD is turned ON, the up/down function can be used based on the analog
signal held by this function as reference data.
When “
” is specified for Up/down
memory mode selection (
), the result
of up/down processing can be stored in
memory.
If the inverter power is turned on or the
RS terminal turned off with the AHD
terminal left turned on, the data held
immediately before power on or turning
off the RS terminal will be used.
Set frequency remains when the inverter is switched with SET terminal with AHD on.
Turn AHD terminal off to re-hold the set frequency.
Frequent use of this function may result in a shorter in memory component of the
inverter.
Option
Code
Terminal
Symbol
Function Name
State
Description
AHD
Analog command hold
ON
Hold the analog input value
OFF Does not hold the analog input value
Valid for inputs:
~
Example (default input configuration
shown
—see
page 3-85
):
See I/O specs on
page 4
–6.
Required settings
Notes:
AHD
Analog
input
command
ON
Hold the data
Frequency
command
AHD
7
6
5
4
3
2
1
L
P24
PLC
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......