E
3
Installation
According to the safety standard listed above, please install referring to the example.
Please be sure to use the both GS1 and GS2, and construct the system that GS1
andGS2 are both turned off when safety input is given to the inverter. Be sure to carry
out the proof test when installation is ready before operation.
When the Gate Suppress function is utilized, connect the drive to a safety certified
interrupting device utilizing EDM output signal to reconfirm both safety inputs GS1
and GS2. Follow the wiring instructions in the Instruction manual.
Components to be combined
Followings are the example of the safety devices to be combined.
Series
Model
Norms to comply
reference certificate
GS9A
301
ISO13849-2 cat4, SIL3
06.06.2007
G9SX
GS226-T15-RC
IEC61508 SIL1-3
04.11.2004
NE1A
SCPU01-V1
IEC61508 SIL3
27.09.2006
In combination with the safety device complying with the class complying PL=d,
PL=d of the inverter is to be achieved.
Safety Related Part
PWR
ERR
G9SX
-
AD
EI
T2
ED
T1
FB
PWR
ERR
G9SX
-
AD
EI
T2
ED
T1
FB
S14
S24
T31
T33
KM1
M
Inverter
with
Safety stop
function
Safety
Unit
(certificated
acc. to EN954
-
1
and ISO13849
-
1)
Safety
Output
EDM
(
Feedback)
input
GS2
GS1
EDM
CM2
Safety
I
n
put
Safety
I
n
put
Manual
Reset
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......