B
32
Register
No.
Function name
Function code R/W
Monitoring and setting items
Data
resolution
1226h
Multi-speed freq. 8
A028 (high)
R/W 0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
1227h
A028 (low)
R/W
1228h
Multi-speed freq. 9
A029 (high)
R/W 0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
1229h
A029 (low)
R/W
122Ah
Multi-speed freq. 10
A030 (high)
R/W 0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
122Bh
A030 (low)
R/W
122Ch
Multi-speed freq. 11
A031 (high)
R/W 0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
122Dh
A031 (low)
R/W
122Eh
Multi-speed freq. 12
A032 (high)
R/W 0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
122Fh
A032 (low)
R/W
1230h
Multi-speed freq. 13
A033 (high)
R/W 0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
1231h
A033 (low)
R/W
1232h
Multi-speed freq. 14
A034 (high)
R/W 0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
1233h
A034 (low)
R/W
1234h
Multi-speed freq. 15
A035 (high)
R/W 0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
1235h
A035 (low)
R/W
1236h
(Reserved)
-
-
-
-
1237h
(Reserved)
-
-
-
-
1238h
Jog frequency
A038
R/W 0.0, "Start frequency" to 999(10000)
0.01 [Hz]
1239h
Jog stop mode
A039
R/W
0 (free-running after jogging stops [disabled
during operation])
1 (deceleration and stop after jogging stops
[disabled during operation])
2 (DC braking after jogging stops [disabled
during operation])
3 (free-running after jogging stops [enabled
during operation])
4 (deceleration and stop after jogging stops
[enabled during operation])
5 (DC braking after jogging stops [enabled
during operation])
-
123Ah
(Reserved)
-
-
-
-
123Bh
Torque boost method
selection
A041
R/W
0 (manual torque boost), 1 (automatic torque
boost)
-
123Ch
Manual torque boost value
A042
R/W 0 to 200
0.1 [%]
123Dh
Manual torque boost
frequency
A043
R/W 0 to 500
0.1 [%]
123Eh
V/F characteristic curve
selection, 1st motor
A044
R/W
0 (VC), 1 (VP), 2 (free V/f), 3 (sensorless
vector control),
-
123Fh
V/f gain
A045
R/W 20 to 100
1 [%]
1240h
Voltage compensation gain
setting for automatic torque
boost, 1st motor
A046
R/W 0 to 255
1 [%]
1241h
Slippage compensation gain
setting for automatic torque
boost, 1st motor
A047
R/W 0 to 255
1 [%]
1242h
to1244h
(Reserved)
-
-
-
-
1245h
DC braking enable
A051
R/W
0 (disabling), 1 (enabling), 2 (output freq <
[A052])
-
1246h
DC braking frequency
A052
R/W 0 to 6000
0.01 [Hz]
1247h
DC braking wait time
A053
R/W 0 to 50
0.1 [sec.]
1248h
DC braking force during
deceleration
A054
R/W 0 to 100
1 [%]
1249h
DC braking time for
deceleration
A055
R/W 0 to 600
0.1 [sec.]
124Ah
DC braking/edge or level
detection for [DB] input
A056
R/W 0 (edge operation), 1 (level operation)
-
124Bh
DC braking force for starting
A057
R/W 0 to 100
1 [%]
124Ch
DC braking time for starting
A058
R/W 0 to 600
0.1 [sec.]
124Dh
DC braking carrier frequency
setting
A059
R/W 20 to 150
0.1 [kHz]
124Eh
(Reserved)
-
-
-
-
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......