Ver.2
27
Register
No.
Function name
Function code
R/W
Monitoring and setting items
Data resolution
124Fh
Frequency upper limit
A061 (high)
R/W
0 or "maximum frequency limit" to "maximum
frequency"
0.01 [Hz]
1250h
A061 (low)
R/W
1251h
Frequency lower limit
A062 (high)
R/W
0 or "maximum frequency limit" to "maximum
frequency"
0.01 [Hz]
1252h
A062 (low)
R/W
1253h
Jump freq. (center) 1
A063 (high)
R/W
0 to 40000(100000)
0.01 [Hz]
1254h
A063 (low)
R/W
1255h
Jump freq. width
(hysteresis) 1
A064
R/W
0 to 1000(10000)
0.01 [Hz]
1256h
Jump freq. (center) 2
A065 (high)
R/W
0 to 40000(100000)
0.01 [Hz]
1257h
A065 (low)
R/W
1258h
Jump freq. width
(hysteresis) 2
A066
R/W
0 to 1000(10000)
0.01 [Hz]
1259h
Jump freq. (center) 3
A067 (high)
R/W
0 to 40000(100000)
0.01 [Hz]
125Ah
A067 (low)
R/W
125Bh
Jump freq. width
(hysteresis) 3
A068
R/W
0 to 1000(10000)
0.01 [Hz]
125Ch
Acceleration hold frequency
A069 (high)
R/W
0 to 40000
0.01 [Hz]
125Dh
A069 (low)
R/W
125Eh
Acceleration hold time
A070
R/W
0 to 600
0.1 [s]
125Fh
PID Function Enable
A071
R/W
0 (disabling), 1 (enabling), 2 (enabling
inverted-data output)
-
1260h
PID proportional gain
A072
R/W
0 to 2500
0.10
1261h
PID integral time constant
A073
R/W
0 to 36000
0.1 [s]
1262h
PID derivative gain
A074
R/W
0 to 10000
0.01 [s]
1263h
PV scale conversion
A075
R/W
1 to 9999
0.01
1264h
PV source
A076
R/W
0 (input via OI), 1 (input via O), 2 (external
communication), 3 (pulse train frequency input),
10 (operation result output)
-
1265h
Reverse PID
A077
R/W
00 (disabling), 01 (enabling)
-
1266h
PID output limiter
A078
R/W
0 to 1000
0.1 [%]
1267h
PID feed forward selection
A079
R/W
0 (disabled), 1(O input), 2 (OI input)
-
1268h
(Reserved)
-
R/W
-
-
1269h
AVR function select
A081
R/W
0 (always on), 1 (always off), 2 (off during
deceleration)
-
126Ah
AVR voltage select
A082
R/W
200 V class: 0 (200)/1 (215)/2 (220)/3 (230)/4
(240)
400 V class: 5 (380)/6 (400)/7 (415)/8 (440)/9
(460)/ 10 (480)
-
126Bh
AVR filter time constant
A083
R/W
0.000 to 10.00
0.001[s]
126Ch
AVR deceleration gain
A084
R/W
50 to 200
1[%]
126Dh
Energy-saving operation
mode
A085
R/W
0 (normal operation), 1 (energy-saving operation)
-
126Eh
Energy-saving mode tuning
A086
R/W
0 to 1000
0.1 [%]
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......