3
42
Add Frequency
–
The inverter can add or subtract on offset value to the output
frequency setting which is specified by
(will work with any of the five possible
sources). The ADD Frequency is a value you can store in parameter
. the ADD
Frequency is summed with or subtracted from the output frequency setting only when
the [ADD] terminal is ON. Function
selects whether to add or subtract. By
configuring an intelligent input as the [ADD] terminal, your application can selectively
apply the fixed value in
to offset (positively or negatively) the inverter output
frequency in real time.
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Initial data
Units
ADD frequency
An offset value that is applied
to the output frequency when
the [ADD] terminal is ON.
Range is 0.0 to 400.0 Hz
Two options:
Plus (adds
value to
the output frequency
setting)
Minus (subtracts
value from the output
frequency setting)
0.00
Hz
ADD direction select
00
Keypad potentiometer
Control terminal
Function
setting
ModBus network input
Calculate function output
Σ
+
Frequency source setting
Output frequency setting
ADD frequency
ADD direction select
+/-
Intelligent input
[ADD]
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......