“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Initial data
Units
PID FBV output
low limit
When the PV goes below this
value, the PID loop turns ON the
PID second stage output, range is
0.0 to 100%
0.0
%
Over-torque/under-torque
selection
Two option codes:
Over-torque
Under-torque
00
Over/under-torque level
(Forward powering mode)
Set range is 0 to 200%
100.
%
Over/under-torque level
(Reverse regen. mode)
Set range is 0 to 200%
100.
%
Over/under-torque level
(Reverse powering mode)
Set range is 0 to 200%
100.
%
Over/under-torque level
(Forward regen. mode)
Set range is 0 to 200%
100.
%
Signal output mode of
Over/under-torque
Two option codes:
During accel., decel. and
constant speed
During constant speed only
01
Electronic thermal
warning level
Set range is 0 to 100%
Setting 0 means disabled.
90
%
Zero speed detection level Set range is 0.0 to 100.0Hz
0.00
Hz
Heat sink overheat
warning
Set range is 0 to 110
C
100.
C
Overload warning level 2 Sets the overload warning signal
level between 0% and 200% (from
0 to two time the rated current of
the inverter)
Rated current
x 1.15
A
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......