4
35
Force Operation from Digital Operator
This function permits a digital operator interface to override the following two settings
in the inverter:
- Frequency source
- Run command source
When using the [OPE] terminal input, typically A001 and
are configured for
sources other than the digital operator interface for the output frequency and Run
command sources, respectively. When the [OPE] input is ON, then user has immediate
command of the inverter, to start or stop the motor and to set the speed.
Option
Code
Terminal
Symbol
Function Name
State
Description
OPE
Force Operation
from Digital
Operator
ON
Forces the operator interface to override:
- Frequency Source Setting, and
- Run
Command Source Setting
OFF
Parameters
and
are in effect again,
for the frequency source and the Run command
source, respectively
Valid for inputs:
~
Example (default input configuration shown
—see
page 3-85
):
See I/O specs on
page 4
–6.
Required settings
(set not equal to
)
(set not equal to
)
Notes:
When changing the [OPE] state during Run Mode
(inverter is driving the motor), the inverter will stop
the motor before the new [OPE] state takes effect.
If the [OPE] input turns ON and the digital
operator gives a Run command while the inverter
is already running, the inverter stops the motor.
Then the digital operator can control the motor.
OPE
7
6
5
4
3
2
1
L
P24
PLC
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......