3
52
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Initial data
Units
Overload restriction
operation mode
Select the operation mode during
overload conditions, four options,
option codes:
Disabled
Enabled for acceleration and
constant speed
Enabled for constant speed
only
Enabled for acceleration and
constant speed, increase speed
at regen.
01
Overload restriction
operation mode, 2
nd
motor
01
Overload restriction level
Sets the level of overload
restriction, between 20% and 200%
of the rated current of the inverter,
setting resolution is 1% of rated
current
Rated
current
x 1.5
Amps
Overload restriction level,
2
nd
motor
Rated
current
x 1.5
Amps
Deceleration rate at
overload restriction
Sets the deceleration rate when
inverter detects overload, range is
0.1 to 3000.0, resolution 0.1
1.0
sec.
Deceleration rate at
overload restriction, 2
nd
motor
1.0
sec.
Overload restriction
operation mode 2
Select the operation mode during
overload conditions, four options,
option codes:
Disabled
Enabled for acceleration and
constant speed
Enabled for constant speed
only
Enabled for acceleration and
constant speed, increase speed
at regen.
01
Overload restriction level 2 Sets the level of overload
restriction, between 20% and 200%
of the rated current of the inverter,
setting resolution is 1% of rated
current
Rated
current
x 1.5
Amps
Deceleration rate 2 at
overload restriction
Sets the deceleration rate when
inverter detects overload, range is
0.1 to 3000.0, resolution 0.1
1.0
sec.
OC suppression selection * Two option codes:
Disabled
Enabled
00
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......