Input Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description
BOK
Brake confirmation
ON
Brake wait time (
) is valid
OFF Brake wait time (
) is not valid
LAC
LAD cancellation
ON
Set ramp times are ignored. Inverter output
immediately follows the freq. command.
OFF Accel. and/or decel. is according to the set ramp time
PCLR
Pulse counter clear
ON
Clear the position deviation data
OFF Maintain the position deviation data
ADD
ADD frequency enable ON
Adds the
(add frequency) value to the output
frequency
OFF Does not add the
value to the output frequency
F-TM
Force Terminal Mode
ON
Force inverter to use input terminals for output
frequency and Run command sources
OFF Source of output frequency set by
and source of
Run command set by
is used
ATR
Enable torque
command input
ON
Torque control command input is enabled
OFF Torque control command input is disabled
KHC
Clear watt-hour data
ON
Clear watt-hour data
OFF No action
MI1
General purpose input
(1)
ON
General purpose input (1) is made ON under EzSQ
OFF General purpose input (1) is made OFF under EzSQ
MI2
General purpose input
(2)
ON
General purpose input (2) is made ON under EzSQ
OFF General purpose input (2) is made OFF under EzSQ
MI3
General purpose input
(3)
ON
General purpose input (3) is made ON under EzSQ
OFF General purpose input (3) is made OFF under EzSQ
MI4
General purpose input
(4)
ON
General purpose input (4) is made ON under EzSQ
OFF General purpose input (4) is made OFF under EzSQ
MI5
General purpose input
(5)
ON
General purpose input (5) is made ON under EzSQ
OFF General purpose input (5) is made OFF under EzSQ
MI6
General purpose input
(6)
ON
General purpose input (6) is made ON under EzSQ
OFF General purpose input (6) is made OFF under EzSQ
MI7
General purpose input
(7)
ON
General purpose input (7) is made ON under EzSQ
OFF General purpose input (7) is made OFF under EzSQ
AHD
Analog command hold ON
Analog command is held
OFF Analog command is not held
CP1
Multistage-position
switch (1)
ON
Multistage position commands are set according to
the combination of these switches.
OFF
CP2
Multistage-position
switch (2)
ON
OFF
CP3
Multistage-position
switch (3)
ON
OFF
ORL
Limit signal of homing
ON
Limit signal of homing is ON
OFF Limit signal of homing is OFF
ORG
Trigger signal of
homing
ON
Starts homing operation
OFF No action
SPD
Speed/position
changeover
ON
Speed control mode
OFF Position control mode
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......