4
46
Multistage-position switch (1)~(3)
When “
(CP1)” to “
(CP3)” are assigned to input terminals, you can select position
settings from multistage positions 0 to 7.
Use multistage position settings 0 to 7 (
to
) for the position settings. If no
position settings are assigned to terminals, multistage position 0 (
) is assumed.
Position setting
Parameter
CP3
CP2
CP1
Multistage position 0
0
0
0
Multistage position 1
0
0
1
Multistage position 2
0
1
0
Multistage position 3
0
1
1
Multistage position 4
1
0
0
Multistage position 5
1
0
1
Multistage position 6
1
1
0
Multistage position 7
1
1
1
You can specify a delay to be applied at multistage position setting input, until the
relevant terminal input is determined. Use this specification to prevent the application
of fluctuating terminal input before it is determined.
You can adjust the determination time with the multistage speed/position
determination time setting (
). The input data is finally determined when the
terminal input becomes stable after the delay set as
. (Note that a long
determination time deteriorates the input terminal response.)
Option
Code
Terminal
Symbol
Function Name
State
Description
~
CP1~CP3
Multistage-position switch
(1)~(3)
ON
Multistage position is defined by combination of
the inputs.
OFF
Valid for inputs:
~
Example (default input configuration
shown
—see
page 3-85
):
See I/O specs on
page 4
–6.
Required settings
~
Notes:
Position
command
ON
ON
ON
CP1
CP2
CP3
1
3
7
5
4
Determination time (
)=0
Determination time
(
) specified
Determination time (
)
CP3
CP2
CP1
7
6
5
4
3
2
1
L
P24
PLC
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......