3
34
PID deviation output
–
If PID deviation "
" exceeds the value in
, output signal
configured as
(OD) is activated.
PID feedback comparison output
–
If PID feedback is out of the range between
and
output signal configured as
(FBV) is activated.
PID scaling
–
When PID scale parameter (
) is set, following variables are scaled.
(monitored) = (variable)
×(
A075
)
d004
F001
A011
A012
A020
A220
A021
A022
A023
A024
A025
A026
A027
A028
A029
A030
A031
A032
A033
A034
A035
A101
A102
A145
PID Sleep Function
The inverter shuts off the output when the PID output becomes less than the specified
value (
) in case of PID is set enabled, or shuts off when the frequency command
becomes less than the specified value in case of PID is set disabled. And if the PID
output or frequency command exceeds the specified value (
) for a specified period
(
), inverter automatically restarts the operation. This is the PID sleep function.
PID Sleep function is always enabled, even the PID function is disabled.
PID output
PID sleep function
triggering level
Run command (internal)
Run
Stop
Run
Run command (external)
Run
PID sleep function action delay time
PID feedback
PID FBV output high limit
PID FBV output low limit
Time
FW input
FBV output
ON
ON
ON
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......