B
7
Data:
A function command is set here.
The data format used in the X200
2
series is corresponding to the Modbus data
format below.
Name of Data
Description
Coil
Binary data that can be referenced and changed ( 1 bit long)
Holding Register
16-bit data that can be referenced and changed
Function code:
Specify a function you want to make the inverter execute. Function codes available to
the X200
2
series are listed below.
Function
Code
Function
Maximum data size
(bytes available
per message)
Maximum number of
data elements available
per message
0 1 h
Read Coil Status
4
32 coils (in bits)
0 3 h
Read Holding Resistor
32
16 registers (in bytes)
0 5 h
Write in Coil
2
1 coil (in bits)
0 6 h
Write in Holding Register
2
1 register (in bytes)
0 8 h
Loopback Test
0 F h
Write in Coils
4
32 coils (in bits)
1 0 h
Write in Registers
32
16 registers (in bytes)
17
h
Read/Write Holding Registor
32
16 registers (in bytes)
Error check:
Modbus-RTU uses CRC (Cyclic Redundancy Check) for error checking.
The CRC code is 16-bit data that is generated for 8-bit blocks of arbitrary length.
The CRC code is generated by a generator polynomial CRC-16 (X16+ X15+ X2+ 1).
Header and trailer (silent interval):
Latency is the time between the reception of a query from the master and transmission
of a response from the inverter.
3.5 characters (24 bits) are always required for latency time. If the latency time
shorter than 3.5 characters, the inverter returns no response.
The actual transmission latency time is the sum of silent interval (3.5 characters
long) + C078 (transmission latency time).
Summary of Contents for WJ200-001L
Page 2: ......
Page 3: ......
Page 49: ......
Page 299: ......
Page 300: ...5 1 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 5 ...
Page 305: ......
Page 328: ...A 1 Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 387: ......
Page 509: ......
Page 665: ......
Page 673: ......