94
Rockwell Automation Publication 2198-UM002E-EN-P - February 2018
Chapter 5
Connect the Kinetix 5700 Drive System
Figure 58 - Corner-grounded Power Configuration (Delta Secondary)
Refer to
beginning on
for input power
interconnect diagrams.
L3
L1
L2
L3 L2 L1
Transformer (Delta) Secondary
Bonded Cabinet
Ground
Transformer
Ground Grid or
Power Distribution Ground
Connect to drive module
ground stud.
Three-phase
AC Line Filter
Circuit
Protection
2198-P
xxx
DC-bus Power Supply
(bottom view)
M1
Contactor
IMPORTANT
Even though impedance-grounded and corner-grounded power
configurations have a ground connection, treat them as ungrounded when
installing Kinetix 5700 drive systems.