Rockwell Automation Publication 2198-UM002E-EN-P - February 2018
247
Kinetix 5700 Safe Torque-off Function
Chapter 9
Safe Torque-off Status
This section describes the safety related status data that is available to the
motion controller.
When a Kinetix 5700 add on profile (AOP) is added to a Logix Designer
application I/O tree, axis tags are added to the controller tags.
This table lists the safety related STANDARD tags that are added when a new
AXIS_CIP_DRIVE axis is defined.
IMPORTANT
The status data described in this section is STANDARD data (not SAFETY
data) and cannot be used as part of a safety function.
Table 123 - Safety Related Axis Tags
Logix Designer Tag Name
Attribute [bit]
Type
Description
AxisFaults
34
DINT
GuardFaultStatus
[5]
BOOL
STO fault - Hardwired
SafetyFaultStatus
[8]
BOOL
STO fault - Integrated
ModuleFaults
163
DINT
GuardStatus
980
DINT
GuardOKStatus
[0]
BOOL
Not STO fault - Hardwired
GuardGateDriveOutputStatus
[2]
BOOL
Torque allowed - Hardwired
GuardStopInputStatus
[3]
BOOL
Safety inputs active - Hardwired
GuardStopRequestStatus
[4]
BOOL
Safety input requesting STO - Hardwired
GuardFault
981
DINT
GuardStopInputFault
[9]
BOOL
STO fault - Hardwired
GuardGateDriveFault
[2]
BOOL
Internal STO circuit fault - Hardwired
CIPAxisFaultsRA
903
DINT
SafetyModuleCommunicationErrorFault
[28]
BOOL
Loss of communication to safety control
CIPAxisAlarmsRA
904
DINT
SafetyModuleCommunicationErrorAlarm
[28]
BOOL
Loss of communication to safety control
CIPInitializationFaultsRA
910
DINT
InvalidSafetyFirmwareFault
[14]
BOOL
Invalid safety control firmware
CIPStartInhibits
676
DINT
SafeTorqueOffActiveInhibit
[5]
BOOL
Torque disabled - Integrated
CIPStartInhibitsRA
912
DINT
SafeTorqueOffInhibit
[5]
BOOL
Torque disabled - Hardwired
AxisSafetyState
760
DINT
Safety supervisor state
AxisSafetyStatus
(1)
761
DINT
SafetyFaultStatus
[0]
BOOL
Status of SI.SafetyFault
SafetyResetRequestStatus
[1]
BOOL
Status of SO.ResetRequest
SafetyResetRequiredStatus
[2]
BOOL
Status of SI.ResetRequired
SafeTorqueOffActiveStatus
[3]
BOOL
Status of SO.SafeTorqueOff