Kinetix 5700 Safe Torque-off Function
Chapter 9
Safe Torque-off Mode
You can use the attribute STO Mode to check if the Kinetix 5700 inverter is in
STO Bypass mode.
Table 126 - Safe Torque-off Mode: MSG
Table 127 - Safe Torque-off Mode: Values
Safe Torque-off Faults
When a safety fault is indicated in any of the following tags:
• SI.SafetyFault
• Axis.SafetyFaultStatus
• Axis.SafetyTorqueOffFault
The cause of the fault can be read using an explicit message.
Table 128 - Safe Torque-off Fault Type: MSG
Table 129 - Safe Torque-off Fault Type: Values
Parameter
Value
Description
Service Code
0x0E
Get attribute single
Class
0x5A
Safety stop functions
Instance
1 or 2
Inverter axis number
Attribute
0x104
STO mode
Data Type
SINT
Short integer
Value
Definition
1
Normal operation
2
STO bypass mode
Parameter
Value
Description
Service Code
0x0E
Get attribute single
Class
0x5A
Safety stop functions
Instance
1 or 2
Inverter axis number
Attribute
0x108
STO fault type
Data Type
SINT
Short integer
Value
Definition
1
No Fault
3
Circuit Error
104
Hardwired input in Network mode