Rockwell Automation Publication 2198-UM002E-EN-P - February 2018
123
Connect the Kinetix 5700 Drive System
Chapter 5
Single-axis Inverter Power/Brake Cable Installation
Single-axis inverters include a two-position cable-shield clamp for 2090-
CPBM7DF cables with 10, 8, 6, 4, and 2 AWG power conductors.
2090-CPBM7DF (series B) 10 AWG cables are designed for use with
Kinetix 5700 single-axis inverters and do not require any modifications.
For single-axis inverters, the 2090-CPBM7DF (series A) cable power
conductors, 102 mm (4.0 in.), require adjustment only when the smaller
(upper position) clamp is used. The upper position is for smaller cables (10, 8,
and 6 AWG). The lower position is for larger cables (4 and 2 AWG). We
recommend that you measure from the edge of the cable jacket (that is covered
with heat shrink) and trim the power conductors as shown in
Table 67 - Power Conductor Trimmed Length
The (series A) 2090-CPBM7DF brake conductor length, 635 mm (25 in.) is
longer than necessary. Measure from the edge of the heat shrink and trim the
brake conductors as shown in
Table 68 - Brake Conductor Trimmed Length
See
on
for a typical series-A installation example. For strip
lengths and torque values, see
and
.
SHOCK HAZARD:
To avoid hazard of electrical shock, make sure shielded
power cables are grounded according to recommendations.
Power Conductor Size
AWG
Power Conductor Length
mm (in.)
6 and 8
75 (2.9)
10
No trimming required
2 and 4
85 (3.3)
Power Conductor Size
AWG
Brake Conductor Length
mm (in.)
6, 8, 10
315 (12.4)
2 and 4
375 (14.7)